ARDENT Commercial Electric Boiler
The ARDENT commercial electric boiler range, encompassing wall-hung and floor-standing variants with heat outputs from 9 to 100 kW, provides an easy-to-integrate, high capacity, reliable, and compact response for electric hot water and central heating demands in commercial buildings.
ARDENT is designed to serve as an indirect water heater or heating system. Multiple electric heating elements immersed into ARDENT’s integrated water storage tank provide a rapid and reliable source of thermal energy for those seeking to avoid a reliance on gas energy supplies.
Features & Key Technologies
- 9-36 kW heat output wall-hung
- 60-100 kW heat output floor-standing
- Simple integration into existing system
- Built-in redundancy
- Avoid reliance on gas energy supplies
- Ideal for all electric-only and hybrid hot water systems
Options
ARDENT S36 | P9 | P12 |P24
The compact wall-hung ARDENT commercial electric boiler is available in two ranges:
ARDENT Standard
The ARDENT Standard 24 kW and 36 kW models features three heating elements with thermostat input and output control to an external pump.
ARDENT Premium
The ARDENT Plus 9 kW, 12 kW and 24 kW models feature two or three heating elements with six or nine circuits controlled by the front-mounted controller with LCD display.
ARDENT S60 | S80 | S100
For larger-scale applications, the ARDENT commercial electric boiler is also available as a floor-standing appliance with 60 kW, 80 kW and 100 kW heat outputs.
Stepped element control is included, as well as an automatic air relief valve, safety valve, and temperature and pressure sensors. The integral controller boasts an LCD display and fault output.
Floor-standing ARDENT appliances offer rear flanged pipework connections and boast a protective IP20-rated outer shell.
Additional Information
ARDENT perfectly integrates with a heat pump to provide an additional high-temperature energy source for water heating during the coldest months.
Or, as part of an indirect hot water system, can help eliminate scale build-up common on direct electrical immersion heaters.
Download the ARDENT Range brochure
The Adveco ARDENT brochure provides you with a quick and easy reference guide to this range of compact and highly efficient, wall-mounted and floor-standing electric boilers.
Limescale Protection In Electric DHW Systems
Read our handbook on how ARDENT can be employed to reduce damaging limescale formation in hard water areas when moving to commercial-grade all-electric water heating.
Technical Specifications & Downloads
ARDENT Electric Boiler tabs
-
Literature
-
Specifications
-
Certification and Ecodesign
Adveco ARDENT 9-36 kW Data Sheet
Adveco ARDENT 60-100 kW Data Sheet
Adveco ARDENT Electric Boiler Range brochure
Adveco Technology Supplement - Electric Boiler Versus Immersion Water Heating
Limescale Protection In Electric Domestic Hot Water- Adveco Handbook
Adveco ARDENT S24-S36 Installation, Operation, and Maintenance Manual
Adveco ARDENT P9-P12-P24 Installation, Operation, and Maintenance Manual
Adveco ARDENT S60 Installation, Operation, and Maintenance Manual
Adveco ARDENT S80–S100 Installation, Operation, and Maintenance Manual
Adveco ARDENT P9-P24 Electric Boiler Engineering Specification
Adveco ARDENT S24-S36 Electric Boiler Engineering Specification
Adveco ARDENT S60-S100 Electric Boiler Engineering Specification
Model |
S24 |
S36 |
P9 |
P12 |
P24 |
S60 |
S80 |
S100 |
Heat Output Range kW |
24.0 |
36.0 |
9.0 |
12.0 |
24.3 |
60 |
80 |
100 |
Element Configuration |
3 x 8.0 |
3 x 12.0 |
6 x 1.5 |
6 x 2.0 |
9 x 2.7 |
10 x 6.0 |
10 x 8.0 |
10 x 10.0 |
Power Supply (3 phase) (Vac / Hz) |
400/50 |
400/50 |
240/1phase /50 |
400/50 |
400/50 |
400/50 |
400/50 |
400/50 |
Fuse requirements (A) |
3 x 40 |
3 x 63 |
50A (1 phase)
|
25 |
40 |
3 x 90 |
3 x 125 |
3 x 160 |
Inlet & Outlet Connections |
1" (DN 25mm) |
1" (DN 25mm) |
G 3/4" |
G 3/4" |
G 3/4" |
PN16 (DN50mm) |
DN50mm PN16 |
DN50mm PN16 |
Boiler Water Volume (L) |
14.2 |
21 |
12.5 |
12.5 |
12.5 |
95 |
95 |
95 |
Maximum Operating Temperature (°C) |
80 |
80 |
80 |
80 |
80 |
90 |
90 |
90 |
Operating Pressure Range (Bar) |
0.5-3.0 |
0.5-3.0 |
0.8 - 2.2 |
0.8-2.2 |
0.8-2.2 |
0.4-3.6 |
0.4-3.6 |
0.4-3.6 |
Energy Efficiency Class |
D |
D |
D |
D |
D |
D |
D |
D |
Dimensions H x W x D (mm) |
600x450x162 |
600x450x215 |
700x430x230 |
700x430x230 |
700x430x230 |
1240x500x900 |
1240x500x900 |
1240x500x900 |
Dry mass (kg) |
13.5 |
17.2 |
25 |
25 |
25 |
92 |
106 |
120 |
Contact Us
Why Choose Adveco
50 Years
Adveco Ltd. is the independent hot water specialist for the commercial built environment and has historically traded as A.O. Smith Water Heaters in the UK.
Highest quality products and services
We prioritise our clients’ needs to deliver bespoke, practical systems.
Full aftersales support
Maintenance and service packages, commissioning, spares, warranty and technical support for your application.